1. When an alarm is triggered, the outputs and led's associated with it are actuated, but there is no display on the panel.


Solution: Check in the MVR USW “Tools--Events And Logs--Set Alarm Events”, you can look up their event codes in the designers handbook and tick them off in here and click set. Check "Tools--Mimic Editor", tick "Show alarms" and then write mimic to relay.