Your device page should look something like this:

A screenshot of a computer

AI-generated content may be incorrect. 

This is for a AMC 600 PCM6.1 with DIO 6.1 + AIO 6.1 card

 


 

To add modbusTCP /IP, right click on device (PCM6.1)


Then add an ethernet adapter


A screenshot of a computer

AI-generated content may be incorrect.


Then right click on ethernet and add modbus TCP client


A screenshot of a computer

AI-generated content may be incorrect. 


Then right click on modbus_TCP_Client and add modbus TCP server


A screenshot of a computer

AI-generated content may be incorrect.

 


The IP in Ethernet is what IP/port on the AMC should use to connect to the unit you want to read data from


A screenshot of a computer

AI-generated content may be incorrect.

 


The IP In modbus_TCP_Server is what IP you want to read data from:


A screenshot of a computer

AI-generated content may be incorrect.


To add what values you want to read, go to modbus slave channel and add all the vales you want to read.


A screenshot of a computer

AI-generated content may be incorrect.


To map modbus values to internal variabels go to modbusTCPServer I/O Mapping


A screenshot of a computer

AI-generated content may be incorrect.


Now you should be able to read data from your unit


If everything works correctly all devices should be green in the left side, and you should be able to see data in the mapping page: