General
1) Check individual DG on load, make sure P (KW) value on all phases is positive. If found negative on any phase, reverse the CT polarities. 2) Crosscheck ...
Mon, 18 Sep, 2023 at 3:23 PM
VIEWS When connected to the unit follow these steps to change/add a view
Mon, 18 Sep, 2023 at 3:27 PM
Please see attached step-by-step guide attached.
Wed, 2 Nov, 2022 at 9:40 AM
Please see attached step-by-step guide.
Wed, 2 Nov, 2022 at 9:40 AM
Each diesel generator and shaft generator unit is able to handle 4 Heavy Consumers (HC). Approx 30% of P nominal. Four Heavy Consumers for each unit Fixed...
Mon, 22 Aug, 2022 at 12:31 PM
In case the same Int. Comm. ID is set in different units in the system, the controllers will raise such alarm. Set Int. Comm. ID (CH - 7531) in order a...
Mon, 22 Aug, 2022 at 1:06 PM
In case of an internal battery failure and loss of power to the controller, it will display (self-check: Error 48) in the display. In this way, the oper...
Mon, 18 Sep, 2023 at 3:30 PM
You have four different options to solve the hardware failure on your controller. 1. Send units for repair You send the faulty controllers to the neare...
Thu, 22 Dec, 2022 at 2:07 PM
Guide for battery change ML-2 This is a guide for changing the battery in a ML-2 DEIF controller in event of an internal battery failure (self-check: error...
Tue, 30 Apr, 2024 at 3:40 PM